with cable break detection:
0,5 V < U < 1 V: Pump stops
2 V < U < 3 V:
1 V < U < 3 V:
3 V < U <10 V:
U < 0.5 V:
Control input "PWM"
PWM signal logic 1 (heating):
n/¹/min
max
min
0 5
PWM signal input [%]
< 5:
5-85:
85-93: Pump runs at minimum speed
85-88: Pump runs at minimum speed
93-100:Pump stops (standby)

6.2.5 General functions of the pump

• The pump is equipped with an electronic overload protection function which switches
off the pump in the event of an overload.
• When the power supply is re-established (chapter 10.2), the pump continues to run with
the values set prior to disconnection from the power supply.
36
Pump runs at minimum
speed (starting)
Pump runs at minimum
speed (operation)
Speed varies between
n
and n
(linear)
min
max
Cable break detection,
the pump runs at
minimum speed
(emergency operation)
85 88
93
Pump runs at maximum speed
The speed of the pump
decreases linearly from
n
to n
max
min
(operation)
(starting)
without cable break detection:
U < 1 V:
2 V < U < 3 V:
1 V < U < 3 V:
3 V < U <10 V:
PWM signal logic 2 (solar):
n/¹/min
max
min
100
PWM %
0
7 12 15
PWM signal input [%]
0-7:
7-15:
12-15: Pump runs at minimum speed
15-95: The speed of the pump
> 95:
Pump stops
Pump runs at minimum
speed (starting)
Pump runs at minimum
speed (operation)
Speed varies between
n
and n
(linear)
min
max
95 100
Pump stops (standby)
Pump runs at minimum speed
(operation)
(starting)
increases linearly from
n
to n
min
max
Pump runs at maximum speed
WILO SE 12/2017
PWM %