9.1
Functions of the Stratos IF modules in
single-pump mode
IF-Modul Stratos
Function
Serial digital interface LON for
connecting to LONWORKS
networks, transceiver
FTT 10 A
Serial digital interface PLR for
connecting to building
management system BMS via
Wilo interface converter or
customer's coupling modules
DP interface for an integratable
doublepump function
2 single pumps or
1 double pump
Control input "0...10 V" for
remote adjustment of speed
or set value or set value
Input for potential-free closed
contact with the function
"Ext. Off"
Input for potential-free closed
contact with the function
"Ext. Min"
Operating message SSM as
potential-free opened contact
9.1.1 Electrical specification of digital
interfaces and control inputs/outputs
Serial digital interface LON for connection to LON-
x
WORKS networks:
Transceiver:
FTT 10 A
Neuron ID:
duplicate sticker with barcode
and alphanumeric representa-
tion of the Neuron ID
Protocol:
LONTalk
Serial digital interface PLR for connecting to inter-
x
face converter or company-specific coupling modu-
les:
Wilo-specific point-to-point connection with Wilo
protocol
x
x
x
x
x
x
x
x
x
x
x
x
x
The terminals are locked and resistant to external
voltage.
Dielectric strength: 250 V AC
Input for potential-free closed contact with the
x
function Ext. Off
contact closed:
Pump works in standard mode.
Contact opened:
pump still.
Contact load of the potential-free closed contact:
24 V DC /
10 mA
Dielectric strength: 250 V AC
Input for potential-free closed contact with the
x
function Ext. Min:
contact closed,
Pump works in standard mode.
Contact opened:
Pump runs at fixed min. speed.
Contact load of the potential-free closed contact:
24 V DC / 10 mA
Dielectric strength: 250 V AC
Output as potential-free opened contact with the
x
function operating signal SBM:
Contact closed:
Pump works in the specified
mode.
Contact opened:
Pump still.
Max. permissible contact load of the potential-free
opened contact:
24V AC, 1A.
Control input 0...10V:
x
Input resistance:
>100 kV
Dielectric strength: 24 V
Accuracy:
± 5%
The following functions can be set:
Remote speed
adjustment:
The pump's differential pressure
control is active. The set value
for the differential pressure is
given by the analog voltage
0...10V (Fig 12).
Representation in display:
Remote speed
adjustment:
The pump's differential pressure
control is deactivated. The
pump works as an actuator at a
constant speed specified by the
voltage 0...10V (Fig 12).