Rooftop Air Conditioning System Citysphere
The following approx. values must be obtained:
Outside air
temperature
=Indoor temperature
62.60°F
68.00°F
77.00°F
86.00°F
95.00°F
If different pressure values are obtained, an authorized repair shop must be consulted to investigate the
reasons.
When the pressure test is complete, disconnect the pressure gauges and refit the sealing caps.

6.8.2. Visual inspection

The system must be inspected visually as described in chapter 6.5 when the repairs are complete.
Page 66
Low pressure gauge
2.7 ± 0.2 bar
2.9 ± 0.2 bar
3.3 ± 0.2 bar
4.1 ± 0.2 bar
4.7 ± 0.2 bar
High pressure gauge
8.4 ± 2 bar
9.0 ± 2 bar
10.3 ± 2 bar
11.4 ± 2 bar
12.8 ± 2 bar