6. UPS Operation

Do not start the UPS until the installation is completed.
Make sure the wiring is connected correctly and the power cables are fixed firmly.
Make sure the power stage/module ID have been configured correctly. Refer to section
2-2 Power Stage/Module for details.
Make sure all the breakers are switch OFF.

6-1. AC Startup

Use the following procedures when turning on the UPS from a fully powered-down state.
Step 1: Refer to "2-4. Wiring Terminal View" to connect the power cables and the battery required for the
UPS system.
Step 2: Switch ON the battery breaker.
Step 3: Switch ON the external power switch to power the UPS. Then, LCD panel is displayed as shown
below.
Step 4: Switch ON the input breaker (Q1). The UPS will enter into Standby Mode, if the setting of Bypass
mode is disabled.
Or the UPS will enter into Bypass Mode, if the setting of Bypass mode is enabled