Battery information
Input & Battery voltage information

3-3. Audible Alarm

Description
UPS status
Bypass mode
Battery mode
Fault mode
Warning
Overload
Others
Fault
All

3-4. Single UPS Operation

1. Turn on the UPS with utility power supply (in AC mode)
1) After power supply is connected correctly, set the breaker of the battery pack at "ON" position (the step only
available for long-run model). Then set the line input breaker at "ON" position(for dual input unit, also set the
bypass input breaker at "ON"). At this time the fan is running and the UPS enter to power on mode for
initialization, several seconds later, UPS operates in Bypass mode and supplies power to the loads via the
bypass.
NOTE: When UPS is in Bypass mode, the output voltage will directly power from utility after you switch on the
input breaker. In Bypass mode, the load is not protected by UPS. To protect your precious devices, you should
turn on the UPS. Refer to next step.
2) Press and hold the "ON" button for 0.5s to turn on the UPS and the buzzer will beep once.
3)
A few seconds later, the UPS will enter to AC mode. If the utility power is abnormal, the UPS will operate in
Battery mode without interruption.
NOTE: When the UPS is running out battery, it will shut down automatically at Battery mode. When the utility
power is restored, the UPS will auto restart in AC mode.
2. Turn on the UPS without utility power supply (in Battery mode)
1) Make sure that the breaker of the battery pack is at "ON" position (only for long-run model).
2) Press the "ON" button to set up the power supply for the UPS, UPS will enter to power on mode. After
initialization UPS will enter to No Output mode, then Press and hold the "ON" button for 0.5s to turn on the
UPS, and the buzzer will beep once.
3) A few seconds later, the UPS will be turned on and enter to Battery mode.
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
59
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr –06 14 AA 59 203 47
Indicates the Battery capacity by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates the battery is not connected.
Indicates low battery level and low battery voltage.
Indicates the input voltage or frequency or battery voltage.
Vac: Input voltage, Vdc: battery voltage, Hz: input frequency
Buzzer status
Beeping once every 2 minutes
Beeping once every 4 seconds
Beeping continuously
Beeping twice every second
Beeping once every second
Beeping continuously
Muted
Yes
No
Yes