6. Specifications

INPUT
Voltage
Battery mode
transfer
Low voltage
range
Low line
comeback
Battery mode
High voltage
transfer
range
High line
comeback
Frequency range
Phase
Power factor
OUTPUT
Voltage
AC voltage regulation
Frequency range (synchronized range)
Frequency range (battery mode)
Current crest ratio
Harmonic distortion
AC mode to battery mode
Transfer time
Inverter to Bypass
Inverter to Eco mode
Waveform
Backup time
EFFICIENCY
AC mode
Battery mode
BATTERIES
Battery type
Number
Standard
Model
Recharging time
Charging current (max.)
Charging voltage (max.)
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
81
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr –06 14 AA 59 203 47
E4 LCD Evolution
TT 10K (S)
10 kVA / 9 kW
230 V
176 VAC ± 3% at 100% load / 110 VAC ± 3% at 50% load
(P/N)
230 V
(P/N)
230 V
276 VAC ± 3% at 100% load / 300 VAC ± 3% at 50% load
(P/N)
230 V
266 VAC ± 3% at 100% load / 290 VAC ± 3% at 50% load
(P/N)
≦ 2% THD (linear load) / ≦ 5% THD (nonlinear load)
Zero (when phase lock fails, <4ms interruption occurs from inverter to bypass)
From 5 to 45 minutes depending on connected load
89%
86%
20
(adjustable 18-20)
1.0 A ± 10%
E4 LCD Evolution
E4 LCD Evolution
TT 15K (S)
15 kVA / 13.5 kW
3 Phase + Neutral 380/400/415 V
186 VAC at 100% load / 120 VAC at 50% load
46~54 Hz at 50Hz / 56~64 Hz at 60Hz
3-phase with neutral and ground
≧ 0.99 at 100% load
3 Phase + neutral 380/400/415 V
± 1%
46 ~ 54 Hz at 50 Hz / 56 ~ 64 Hz at 60 Hz
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
3:1 max
Zero
<10 ms
Pure sine wave
89%
88%
12 V / 9 AH
2 x 20
(adjustable 18-20)
9 hours recover to 90% capacity
2.0 A ± 10%
273 VDC ± 1%
E4 LCD Evolution
TT 20K (S)
TT 30K (S)
20 kVA / 18 kW
30 kVA / 27 kW
89%
87%
3 x 20
(adjustable 18-20)
2.0 A ± 10%
4.0 A ± 10%
90%
89%