INFOSEC UPS SYSTEM E4 Evolution II 100k TT S Manuel Utilisateur page 105

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Bypass Frequency
Range
Converter
--
Mode
ECO Mode
--
Bypass Mode
--
Auto-Restart
--
Cold Start
--
Battery Mode
--
Delay Time
System Shutdown Time
Shutdown/
Restore
System Restore Time
Charger Test
--
Redundancy
--
INFOSEC UPS SYSTEM – 15, Rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
104
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 02 19 AA 59 203 07
Set bypass Frequency range:
Upper/ Lower limit
 +/- 1Hz
 +/- 2Hz
 +/- 4Hz (Default)
Set converter mode
 Disable (Default)
 Enable
Set ECO mode
 Disable (Default)
 Enable
Set bypass mode
 Disable
 Enable (Default)
MUST be reviewed after UPS installation.
If you need the Bypass power when UPS is OFF, please enable
it.
Set auto-restart
 Disable
 Enable (Default)
After "Enable" is set, once UPS shutdown occurs due to low
battery and then utility restores, the UPS will return to line mode.
Set cold start
 Disable
 Enable (Default)
After "Enable" is set, the UPS can be turned on without
connecting to utility by pressing Battery Start Button. Refer to
cold start operation for the details. (
Cold Startup.
)
Set system shutdown delay time in battery mode (0~9990sec).
 0: Disable (Default)
 Not 0: Enable
When this feature is enabled, UPS will shut off output after UPS
operates in Battery mode for certain seconds.
Set system shutdown time (0.2~99min)
 0.2 min (Default)
This delay time will start counting when the
CONTROL-Shutdown Restore command is executed.
Set system restore time (0~9999min)
 1 min (Default)
This delay time will start counting after shutdown time is elapsed
when the CONTROL-Shutdown Restore command is executed.
Set charger test
 Disable (Default)
 Enable
Set QTY of redundant UPS (0~1)
 0 (Default)
MUST be set after the UPS in parallel.
Refer to Section 6-2.