System Setup Screen
The System Setup Screen and setting options are shown below. System Settings can only be accessed
when the UPS is operated functioning in specific modes. Please refer to the table below for the details. If an
option is not available under a specific mode, a warning screen will appear such as below.
Setup-System Setting List
Setting Item
Sub Item
Output
--
Voltage
BYPASS
Bypass Voltage Range
SETTING
INFOSEC UPS SYSTEM – 15, Rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
103
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 02 19 AA 59 203 07
Setup-System Screen
Warning Screen
Explanation
Set output voltage
 220Vac
 230Vac (Default)
 240Vac
MUST be reviewed after UPS installation
Set bypass voltage range:
Upper limit
 +10%
 +15% (Default)
 +20%
Lower limit
 -10%
 -20% (Default)
 -30%