3 ELECTRICAL CONNECTIONS

! Risk of injury and material damages due to electric shock !
! Risk of malfunction due to improper installation !
Make the connections by following the indications of the wiring diagram.
WARNING For adequate electrical safety, all cables must have double insulation. Be sure to keep them clearly separated (minimum 4
mm in air or 1 mm through additional insulation) safety extra-low-voltage cables from low-voltage cables (230V ~) by arranging them
within plastic raceways and securing them with appropriate clamps near the terminal blocks.
WARNING For the connection to the network, use multipolar cable of minimum section 3x1,5mm² and the type required by current
regulations. To connect the motors, use cable minimum section 1.5 mm² and the type required by current regulations. By way of example,
if the cable is outside (outdoors), it must be at least equal to H05RN-F while, if inside (in channel), it must be at least equal to H05VV-F.
WARNING All cables should be stripped and unsheathed in the immediate vicinity of the terminals. Keep the cables slightly longer so
that any excess can be removed later.
WARNING Connect the grounding conductor to the appropriate terminal, taking care to keep its length longer than that of the active
conductors so that in the event of the cable coming out of the fixing seat, the active conductors are the first to stretch.
WARNING When connecting the encoder to the control board, use only a dedicated 3x0,22mm² cable.
3 - 4
22 V ~ transformer power supply input or photovoltaic accumulator GREEN ENERGY input.
5 - 6
24 V
7 - 8
Motor Output 1: 24V max 7A (max 10A if only one motor is present)
9
Connection of motors metallic parts
10 - 11
Motor Output 2: 24V max 7A (if present)
12 - 13
24 V
"BOOST" output for electric-lock, max 1 x art. 110 (if P062=0), 24V pulse output, max 5W (if P062=1), step by step (if
14
-
P062=2), electro-brake output for not self-locking operators (if P062=3), output for electric-lock power supply via external
15
+
relay (if P062=4), output for electro-magnets power supply for barriers (ifP062=5) or temporized output (if P062>5).
16 - 17
24 V
18
IN 6
INPUT 6 Configurable Input (See P022 for selectable values)
19
Com
20
IN 5
INPUT 5 Configurable Input (See P021 for selectable values)
21
Com
22
IN 4
INPUT 4 Configurable Input (See P020 for selectable values)
23
Com
24
IN 3
INPUT 3 Configurable Input (See P019 for selectable values)
25
Com
26
IN 2
INPUT 2 Configurable Input (See P018 for selectable values)
27
Com
28
IN 1
INPUT 1 Configurable Input (See P017 for selectable values)
29
Com
Radio antenna signal input
ANT
Radio antenna ground input
32
+
24 V
33
-
1
-
Stabilized 24 V
2
+
F1
See wiring diagram
F2
Fuse T 15A L 250V
ENC_M1
M1 motor encoder input
ENC_M2
M2 motor encoder input
U 1
UART 1 Plug-in module input for NET-NODE and MEMONET
U 2
UART 2 Plug-in module input for NET-EXP
26
NET24N board terminal table
battery power supply
max 15 W output for open gate fix warning light (if P052=0), flashing (if P052=1) or courtesy light (if P052>1)
Flashing light output max 15W
power supply output for auxiliary devices
power supply output for tested safety devices
Encoder selection Jumper (J5=M1 - J9=M2)
A
Position "
" = operators with encoder (remind to set P029=0)
B
Position "
" = operators without encoder (remind to set P029=1)
(24V_AUX + 24V_ST)
=
max 200mA