2)
After the software loading phase the control logic will acquire the system status and the
operation of the RCB switch, and will show the operating sequences. Close the switch
SBCB as requested.
Picture 18 – Bypass start-up
3)
Close the battery switch BCB when indicated by the display.
Picture 19 – Connecting the battery
4)
Close the output switch OCB when required and immediately after the display will require to
open the manual bypass switch MBCB. The inverter will start.
46
OMT87115 REV. B
Installation and start-up of KEOR HPE UPS 400-500 kVA