3 INSTALLATION
Fig. 3.11 Connection of the flow sensor type 8031 to the 8025 panel version
3.7.3 Connection of specific flow sensors (other than 8020/8030)
Refer to the flow sensor documentation in order to select the required voltage supply.
For power supply and output signal connection cf. fig. 3.10 § 3.7.1
with 12...30 VDC power supply of the controller
The flow sensor may be powered with 5...18 VDC, connect terminals 2 (L-) and 4 (L+)
or with 12...30 VDC, connect terminals 2 (L-) and 3 (L+).
with 230/115 VAC power supply of the controller
The flow sensor may be powered with 16 VDC, connect terminals 2 (L-) and 4 (L+)
or with 28 VDC, connect terminals 2 (L-) and 3 (L+).
f the power supply of the sensor is less than 16 VDC, the direct connection of a flow
controller with 115/230 VAC power supply is not possible.
Fig. 3.12 Connection of the specific flow sensor to the 8025 panel version
Sensor connection:
0 V < (L+) - 12 V < 18 V
12 V < L+ < 30 V