6 Configuring the Heat Pump Heating System

The menus for "Outputs", "Inputs", "Special functions" and
"Modem" as well as the extended setting menu can be set at the
configuration level. The extended menu level for technicians is

6.1 Settings

Depending on the system configuration, the full "Settings" menu
contains the following inquiries:
EN-10
called by simultaneously pressing the button combination
(MENU) and (ENTER ↵) (for approx. 5 seconds)
Select the desired menu item with the arrow buttons and confirm
with the ENTER button (↵).
System-specific parameters
Menu for setting the time. An automatic
changeover from daylight saving time
(summer) to winter time can be selected.
Level for setting operating modes
Selects the operating mode
It is also possible to make changes directly
using the modus button.
Duration of party mode in hours
After the set period has elapsed, the system
returns automatically back to automatic
operation again.
Duration of vacation mode in days
After the set period has elapsed, the system
returns automatically back to automatic
operation again.
Level for setting the heat pump
This setting is dependent on the HP type. Refer
to the installation and operating instructions of
the heat pump or the type plate for the relevant
number.
This setting is dependent on the HP type. Refer
to the installation and operating instructions of
the heat pump for the relevant temperature
limit.
This setting is dependent on the HP type. If
necessary, refer to the installation and
operating instructions of the heat pump for the
relevant switching mode.
This setting is dependent on the HP type. If
necessary, refer to the installation and
operating instructions of the heat pump for the
relevant switching mode.
Settings for the 2nd heat generator to
supplement heat pump heating operation in
bivalent and mono energy systems
The 2nd heat generator is only necessary as of
a particular limit temperature depending on the
dimensioning of the heat pump system. The
2nd heat generator is not switched on until the
temperature sinks below the set limit
temperature.
Setting range
Display
International 24 h
Always
display
Always
Cooling
Always
Summer
Auto
Party
Vacation
ZWE
0
Always
... 4 ...
72
0
Always
... 15 ...
150
Always
1
Nonreversible HP
2
-25° C
Air HP
-15° C
NC contact
Always
NO contact
NC contact
Always
NO contact
Bivalent or mono
energy
-20° C
Bivalent or mono
energy
... -5°C ...
+20° C