Alarm
A9
Description
The battery has reached the pre-alarm discharge level.
Possible
 The battery is discharging due to a mains failure.
causes
 Rectifier failure.
Solutions
1. Check which alarms are present and carry out the indicated
procedures.
2. If the alarm persists, contact our Technical Support Service.
Alarm
A10
Description
Fault following a battery test.
Possible
 Battery fault.
causes
Solutions
1. Check the battery.
2. Reset the system.
3. If the alarm persists, contact our Technical Support Service.
Alarm
A11
Description
The current sensor has detected a short-circuit at the output.
Possible
 Load problem.
causes
 Measuring circuit failure.
Solutions
1. Check the loads connected to the UPS output.
2. If the alarm persists, contact our Technical Support Service.
Alarm
A12
Description
Inverter shutdown due to an extended short-circuit during a power failure,
or due to an overcurrent on the inverter bridge input.
Possible
 Short-circuit on the loads during a power failure.
causes
 Inverter bridge fault.
 Temporary current peak.
Solutions
1. Reset the system.
2. If the alarm persists, contact our Technical Support Service.
Manuel de l'utilisateur de l'ASI
BATTERY AUT END
BATTERY FAULT
SHORT CIRCUIT
STOP TIMEOUT SC
UPS user manual