6.7
BATTERY TEST
The BATTERY TEST menu allows to carry out a short discharge test of the battery. In case the battery is
not efficient, the alarm "A10 – Battery fault" is generated at the end of the test.
BATTERY TEST?
BATTERY TEST?
SPECIAL
BATTERY TEST
Possible loss of supply
This test can affect the continuity of supply to the loads if the battery is not fully charged.
6.8
SYSTEM RESET
The UPS is equipped with internal protections which block the system or some of its sections. The alarm
can be cleared and normal operation can be resumed via the RESET menu. In case the failure persists,
the UPS will return to the previous failure condition.
In some cases the RESET is necessary to simply reset a failure signal, then the UPS will resume
operation.
RESET DEVICE?
RESET DEVICE?
SPECIAL
RESET
Manuel de l'utilisateur de l'ASI
NO
(1x)
YES
NO
(1x)
YES
UPS user manual