Technical Data; Performance Data - oventrop Regudis W-HTF Mode D'emploi

Masquer les pouces Voir aussi pour Regudis W-HTF:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4 Technical data

4.1 Performance data

Size:
Max. operating pressure p
Max. operating temperature t
(Heating water – supply)
Min. cold water pressure
without flow limiter
with flow limiter
Min. differential pressure
supply:
Draw off temperature
t
:
draw off
Min. flow temperature:
Connections:
Performance range 1
Nominal draw off quantity (PHW):
Draw off capacity at dT 35K:
Performance range 2
Nominal draw off quantity (PHW):
Draw off capacity at dT 35K:
Performance range 3
Nominal draw off quantity (PHW):
Draw off capacity at dT 35K:
Fluid primary side:
Fluid secondary side:
Pump variable temperature heating circuit:
Wilo- Yonos PARA RS 15/6 RKA 130
Performance range of variable temperature circuits:
Up to 9kW or a heating surface up to 120 m²
with a heat demand of approx. 75 W/m²:
(V
= 1000 l/h and ∆t= 8K)
Heating circuit
NOTICE
The operating instructions of the pump manufacturer
must be observed!
Fluid: Non-aggressive fluids (e.g. water and suitable
water and glycol mixtures according to VDI 2035). Not
suitable for steam, oily and aggressive fluids.
18
DN 20
:
10 bar
s
:
90 °C
s
2.0 bar
2.5 bar
300 mbar
40-70 °C
t
+ 15K
draw off
3
G
collar nut,
4
flat sealing
12 l/min
29 KW
15 l/min
36 KW
17 l/min
42 KW
Heating water
Potable water
DANGER
Suitable measures (e.g. safety valves) have to
be taken to ensure that the maximum operating
pressures and maximum and minimum operating
temperatures are not exceeded or undercut.
If necessary, provide an electric sensor attached
to the pipe to protect the surface heating circuit
from unacceptably high temperatures.
The electric sensor attached to the pipe is to be
connected so that the circulation pump is switched
off if the max. permissible operating temperature
(heating water – supply) is exceeded and the zone
valve in the heating circuit return is closed.
Oventrop offers a suitable sensor attached to the
pipe or actuators (e.g. safety temperature limiter,
item no. 1143000).
Actuator
Illustr. 4.1 System illustration cabling
Circulation
pump
Junction
box
Safety
+
temperature
limiter

Publicité

Table des Matières
loading

Table des Matières