Troubleshooting
Any malfunctions that cannot be removed by means of the measures
described in this chapter may only be repaired by the manufacturer.
Problem
The display shows OFF. Automatic switch off
The display shows the
battery symbol
Display remains blank
The display toggles
between value and "----"
The displayed level is
incorrect
Display toggles between
9999 and "----"
Display shows 0 even
though the level is
higher
Other malfunctions
Troubleshooting
Possible reason
1
after 2
minutes
/
2
The battery voltage is
below critical value
The battery is not con-
nected
The battery connector is
not connected to the
PCB
Incorrect tank data
entered
Incorrect tank data
entered
Line interruption or
probe not connected
Short circuit in the con-
nection cable between
the pressure sensor and
the control unit
-
Repair
Press the function key to
read the liquid level
Replace the battery
(see chapter "Inserting/
connecting the battery")
Connect the battery
(see chapter "Inserting/
connecting the battery")
Check the battery con-
nector
Correct the tank data
(see chapter "Entering
the tank data")
Correct the tank data
(see chapter "Entering
the tank data")
Check the cable and the
probe
Check the cable
Contact the AFRISO
service hotline