2.5. Protection

The charging station can have several protections according to the model, as described below.
CAUTION
In models that do not include protections (FS3NN / FW3NN), they must be installed upstream of the charger
so that each connection point is powered individually by a circuit that is protected by an overvoltage protection
device and a residual current device.
Q3
Q4
FS1MW / FW1MW (single phase with manual protections and
wattmeters)
For both cases:
Q1: Main switch 80 A
Q2, Q5: 30 mA type A residual current circuit breaker
Q3, Q4: Curve C thermal magnetic circuit breaker
Q2 and Q3 protect the left power socket
Q4 and Q5 protect the right power socket
14
Q2
Q5
Q1
Q3
Q4
Q1
FS3MW / FW3MW (three phase with manual protections and
wattmeters)
ABW2011IQM01_D - Installation and Operation Manual