Power cable sizes and fuses
Note: Do not use larger fuses when the input power cable is selected according to
this table.
Type
ACS310-
gG
x = E/U
A
1-phase U
= 200...240 V (200, 208, 220, 230, 240 V)
N
01x-02A4-2
10
01x-04A7-2
16
01x-06A7-2
16/20
01x-07A5-2
20/25
01x-09A8-2
25/35
3-phase U
= 200...240 V (200, 208, 220, 230, 240 V)
N
03x-02A6-2
10
03x-03A9-2
10
03x-05A2-2
10
03x-07A4-2
16
03x-08A3-2
16
03x-10A8-2
16
03x-14A6-2
25
03x-19A4-2
25
03x-26A8-2
63
03x-34A1-2
80
03x-50A8-2
100
3-phase U
= 380...480 V (380, 400, 415, 440, 460, 480 V)
N
03x-01A3-4
10
03x-02A1-4
10
03x-02A6-4
10
03x-03A6-4
10
03x-04A5-4
16
03x-06A2-4
16
03x-08A0-4
16
03x-09A7-4
20
03x-13A8-4
25
03x-17A2-4
35
03x-25A4-4
50
03x-34A1-4
80
03x-41A8-4
100
03x-48A4-4
100
1)
If 50% overload capacity is needed, use the larger fuse alternative.
Fuses
UL Class T
(600 V)
(U1, V1, W1)
A
mm
10
2.5
20
2.5
1)
25
2.5
1)
30
2.5
1)
35
10
2.5
10
2.5
15
2.5
15
2.5
15
2.5
20
2.5
30
6.0
35
6.0
60
10.0
80
16.0
100
25.0
10
2.5
10
2.5
10
2.5
10
2.5
15
2.5
15
2.5
20
2.5
25
2.5
30
6.0
35
6.0
50
10.0
80
16.0
100
25.0
100
25.0
Size of copper conductor in cablings
Supply
(U2, V2, W2)
2
AWG
mm
14
0.75
14
0.75
10
1.5
10
1.5
6
10
2.5
14
1.5
14
1.5
14
1.5
12
1.5
12
1.5
12
2.5
10
6
10
6
8
10
6
16
2
25
14
1.5
14
1.5
14
1.5
12
1.5
12
1.5
12
1.5
12
1.5
12
2.5
10
6
8
6
8
10
6
16
4
16
4
25
Technical data 37
Motor
PE
2
2
AWG
mm
18
2.5
18
2.5
14
2.5
14
2.5
12
6
14
2.5
14
2.5
14
2.5
14
2.5
14
2.5
12
2.5
10
6.0
10
6.0
8
10.0
6
16.0
2
16.0
14
2.5
14
2.5
14
2.5
14
2.5
14
2.5
14
2.5
14
2.5
12
2.5
10
6.0
8
6.0
8
10.0
6
16.0
4
16.0
4
16.0
00578903.xls G
AWG
14
14
10
10
10
14
14
14
12
12
12
10
10
8
6
4
14
14
14
12
12
12
12
12
10
8
8
6
4
4