ABB ACS55 Guide De L'utilisateur page 297

Masquer les pouces Voir aussi pour ACS55:
Table des Matières

Publicité

Actual signals in the short parameter view
Actual signals in the short parameter view
No.
Name/Value
04 FAULT HISTORY
0401 LAST FAULT
Parameters in the short parameter view
Parameters in the short parameter view
No.
Name/Value
11 REFERENCE
SELECT
1105 REF1 MAX
0.0...500.0 Hz
12 CONSTANT
SPEEDS
1202 CONST
SPEED 1
0.0...500.0 Hz
1203 CONST
SPEED 2
0.0...500.0 Hz
1204 CONST
SPEED 3
0.0...500.0 Hz
Actual signals and parameters in the short view 29
Description
Fault history (read-only)
Code of the latest fault. See chapter Fault tracing in ACS310
user's manual (3AUA0000044201 [English]) for the codes.
0 = Fault history is clear (on panel display = NO RECORD).
Description
Panel reference type, external control location selection and
external reference sources and limits
Defines the maximum value for external reference REF1.
Corresponds to the maximum setting of the used source
signal.
Maximum value in Hz. See the example for parameter 1104
REF1 MIN in ACS310 user's manual (3AUA0000044201
[English]).
Constant speed (drive output frequency) selection and
values. By default constant speed selection is made through
digital inputs DI3 and DI4.1 = DI active, 0 = DI inactive.
DI3 DI4 Operation
0
0 No constant speed
1
0 Speed defined by parameter
0
1 Speed defined by parameter
1
1 Speed defined by parameter
For more information, see chapter Program features,
section Constant speeds in ACS310 user's manual
(3AUA0000044201 [English]).
Defines constant drive output frequency 1.
Output frequency in Hz.
Defines constant drive output frequency 2.
Output frequency in Hz.
Defines constant drive output frequency 3.
Output frequency in Hz.
1202
CONST SPEED 1
1203
CONST SPEED 2
1204
CONST SPEED 3
FbEq
1 = 1
Def/FbEq
E: 50.0 Hz
U: 60.0 Hz
1 = 0.1 Hz
E: 5.0 Hz
U: 6.0 Hz
1 = 0.1 Hz
E: 10.0 Hz
U: 12.0 Hz
1 = 0.1 Hz
E: 15.0 Hz
U: 18.0 Hz
1 = 0.1 Hz