30 Actual signals and parameters in the short view
Parameters in the short parameter view
No.
Name/Value
13 ANALOG INPUTS Analog input signal processing
1301 MINIMUM AI1
-
100.0...
100.0%
14 RELAY OUTPUTS Status information indicated through relay output, and relay
1401 RELAY
OUTPUT 1
NOT SEL
READY
RUN
FAULT(-1)
PFC
16 SYSTEM
CONTROLS
1611 PARAMETER
VIEW
FLASHDROP
SHORT VIEW
LONG VIEW
Description
Defines the minimum %-value that corresponds to minimum
mA/(V) signal for analog input AI1. When used as a
reference, the value corresponds to the reference minimum
setting.
0...20 mA
0...100%
=
4...20 mA
20...100%
=
-10...10 mA
-50...50%
=
Example: If AI1 is selected as the source for external
reference REF1, this value corresponds to the value of
parameter 1104 REF1 MIN.
Note:
MINIMUM AI1
value.
Value in percent of the full signal range.
Example: If the minimum value for analog input is 4 mA, the
percent value for 0...20 mA range is:
(4 mA / 20 mA) · 100% = 20%
operating delays. For more information, see chapter Actual
signals and parameters in ACS310 user's manual
(3AUA0000044201 [English]).
Selects a drive status indicated through relay output RO 1.
The relay energizes when the status meets the setting.
Not used
Ready to function: Run enable signal on, no fault, supply
voltage within acceptable range and emergency stop signal
off.
Running: Start signal on, Run enable signal on, no active
fault.
Inverted fault. Relay is de-energized on a fault trip.
Start/stop motor in PFC control. See parameter group 81
PFC CONTROL in ACS310 user's manual
(3AUA0000044201 [English]). Use this option only when
PFC control is used. Selection activated/deactivated when
the drive is not running.
Parameter view, Run enable, parameter lock etc.
Selects the parameter view, ie which parameters are shown
on the control panel.
Shows the FlashDrop parameter list. Does not include the
short parameter list. Parameters which are hidden by the
FlashDrop device are not visible.
FlashDrop parameter values are activated by setting
parameter
9902 APPLIC MACRO
Shows only those signals and parameters that are listed in
this table and the table in section
parameter view
on page 29.
Shows all signals and parameters. See chapter Actual
signals and parameters in ACS310 user's manual
(3AUA0000044201 [English]).
value must not exceed MAXIMUM AI
to 31
(LOAD FD
Actual signals in the short
Def/FbEq
1.0%
1 = 0.1%
FAULT(-1)
0
1
2
3
31
SHORT
VIEW
1
SET).
2
3