16 Electrical installation
Connecting the control cables
Default I/O connection diagram
The default connection of the control signals depends on the application macro in
use, which is selected with parameter
The default macro is the ABB standard macro. It provides a general purpose I/O
configuration with three constant speeds. Parameter values are the default values
given in chapter Actual signals and parameters in ACS310 user's manual
(3AUA0000044201 [English]). For other macros, see I/O connections in chapter
Application macros in the same manual, and default values on page
manual.
The default I/O connections for the ABB standard macro are given in the figure below.
1...10 kohm
max. 500 ohm
1)
See parameter group
SPEEDS:
DI3 DI4 Operation (parameter)
0
0
Set speed through AI1
1
0
Speed 1 (1202)
0
1
Speed 2 (1203)
1
1
Speed 3 (1204)
9902 APPLIC MACRO
X1A
1
SCR
Signal cable shield (screen)
2
AI1
Output frequency reference: 0...10 V
3
GND
Analog input circuit common
4
+10V
Reference voltage: +10 V DC, max. 10 mA
5
AI2
Not in use by default. 0...10 V
6
GND
Analog input circuit common
7
AO
Output frequency value: 0...20 mA
8
GND
Analog output circuit common
3)
9
+24V
Auxiliary voltage output: +24 V DC, max. 200 mA
10 GND
Auxiliary voltage output common
11 DCOM
Digital input common
12 DI1
Stop (0) / Start (1)
13 DI2
Forward (0) / Reverse (1)
14 DI3
Constant speed selection
15 DI4
Constant speed selection
16 DI5
Acceleration and deceleration selection
X1B
17 ROCOM
18 RONC
19 RONO
20 DOSRC
21 DOOUT
22 DOGND
12 CONSTANT
(see page 32).
1)
1)
Relay output 1
No fault [Fault (-1)]
Digital output, max. 100 mA
No fault [Fault (-1)]
2)
0 = ramp times according to parameters
2202
and 2203.
1 = ramp times according to parameters
2205 and 2206.
3)
360 degree grounding under a clamp.
Tightening torque = 0.4 N·m (3.5 lbf·in).
28
in this
2)