Parameters in the short parameter view
No.
Name/Value
LOAD FD SET FlashDrop parameter values as defined by the FlashDrop
USER S1
LOAD
USER S1
SAVE
USER S2
LOAD
USER S2
SAVE
9905 MOTOR NOM
VOLT
200 V units:
115...345 V
400 V E units:
200...600 V
400 V U units:
230...690 V
9906 MOTOR NOM
CURR
0.2...2.0 · I
2N
9907 MOTOR NOM
FREQ
10.0...500.0 Hz Frequency
Actual signals and parameters in the short view 33
Description
file. Parameter view is selected by parameter
PARAMETER
VIEW.
FlashDrop is an optional device for fast copying of
parameters to unpowered drives. FlashDrop allows easy
customization of the parameter list, eg selected parameters
can be hidden. For more information, see MFDT-01
FlashDrop user's manual (3AFE68591074 [English]).
User 1 macro loaded into use. Before loading, check that
the saved parameter settings and the motor model are
suitable for the application.
Save User 1 macro. Stores the current parameter settings
and the motor model.
User 2 macro loaded into use. Before loading, check that
the saved parameter settings and the motor model are
suitable for the application.
Save User 2 macro. Stores the current parameter settings
and the motor model.
Defines the nominal motor voltage. Must be equal to the
value on the motor rating plate. The drive cannot supply the
motor with a voltage greater than the input power voltage.
Note that the output voltage is not limited by the nominal
motor voltage but increased linearly up to the value of the
input voltage.
Output voltage
Input voltage
9905
WARNING! Never connect a motor to a drive which
is connected to power line with voltage level higher
than the rated motor voltage.
Voltage.
Note: The stress on the motor insulations is always
dependent on the drive supply voltage. This also applies to
the case where the motor voltage rating is lower than the
rating of the drive and the supply of the drive.
Defines the nominal motor current. Must be equal to the
value on the motor rating plate.
Current
Defines the nominal motor frequency, ie the frequency at
which the output voltage equals the nominal motor voltage:
Field weakening point = Nom. frequency · Supply voltage /
Motor nom. voltage
1611
Output frequency
9907
Def/FbEq
31
0
-1
-2
-3
200 V
units:
230 V
400 V
E units:
400 V
400 V
U units:
460 V
1 = 1 V
I
2N
1 = 0.1 A
E: 50.0 Hz
U: 60.0 Hz
1 = 0.1 Hz