Miele PRI 210 Mode D'emploi page 26

Repasseuses professionnelles
Masquer les pouces Voir aussi pour PRI 210:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

en - Installation and planning notes
26
sioned additional fan must be installed in the shaft or roof outlet on-
site. Ensure that there is sufficient ventilation in the room where the
ironer is installed
- The connection for the exhaust air duct for steam extraction is lo-
cated on the rear of the left side column and has a diameter of
2 ¾" (70 mm).
- The exhaust air duct must have an internal diameter of
2 ¾" (70 mm).
- To prevent the build-up of condensation in an upward sloping ex-
haust ducting, a ⅛" to ¼" (3 - 5 mm) diameter condensate trap
should be fitted at the lowest point.
- Ensure that there is sufficient ventilation in the room where the
ironer is installed
- The on-site ducting system and the exit point to the outside must
be checked on a regular basis for a build-up of lint and cleaned if
required.
- The air duct leading into the open should be protected against the
elements, e.g. using a suitable hood or grille or with a 90° bend.

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Pri 214Pri 217

Table des Matières