Lockouts
Lockouts
In case of a lockout, a warning sym-
bol (
) and a flashing error code
appears on the display. The cause of
a fault should first be determined
and eliminated before the boiler is
being reset. The table below shows
all possible lockouts with indication
of possible cause.
All manuals and user guides at all-guides.com
DESCRIPTION OF ER-
ERR.
ROR
CODE
10
Outside sensor fault
Boiler temperature 1 sensor
20
fault
Common flow temperature
26
sensor fault
Flue gas temperature sensor
28
fault
Return temperature 1 sensor
40
fault
DHW temperature sensor/
50
thermostat 1 fault
DHW temperature sensor/
52
thermostat 2 fault
78
Water pressure sensor fault
LPB short-circuit or no bus
81
power supply
82
LPB address collision
BSB-Wire short-circuit or no
83
communication
84
BSB-Wire address collision
BSB radio communication
85
fault
91
Data loss in EEPROM
100
Two clock time masters
105
Maintenance message
110
SLT lock-out
Temp limiter safety shut-
111
down
Water pressure switch has
119
cut out
128
Loss of flame in operation
Flue gas temperature max. li-
130
mit exceeded
CAUSE
Outside sensor fault (B9) (room model,
plant frost protection, sensor value not
plausible)
Short-circuit boiler flow sensor (B2)
Open-circuit boiler flow sensor (B2)
Common flow temperature sensor fault
(B10) (sensor missing, double configu-
red, configured on slave, ...)
Open-circuit flue gas sensor
Short-circuit flue gas sensor
Short-circuit boiler return sensor (B7)
Open-circuit boiler return sensor (B7)
DHW temperature sensor/thermostat 1
fault (B3)
DHW temperature sensor/thermostat 2
fault (B31)
water pressure sensor fault (short- or
open-circuit)
LPB short-circuit or no bus power supply
LPB address collision
BSB-Wire short-circuit or no communica-
tion
BSB-Wire address collision
BSB radio communication fault
Data loss EEPROM
Two clock time masters
Maintenance message
SLT-temperature exceeded
open TL/SLT causes lockout
Boiler return temperature is higher than/
equal to (boiler temperature + Sd_RL_
groesser_VL - 2K)
Delta-T too high
Boiler temperature rises faster than allo-
wed in TempGradMax
Temp limiter safety shut-down
Thermostat burner door
Repetition error counter exceeded
Loss of flame in operation
Flue gas temperature ≥ 90˚ C