elco TRIGON XL 300 Notice D'installation Et D'emploi page 23

Masquer les pouces Voir aussi pour TRIGON XL 300:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Installation
Dimensioning single
Max length reduction
Pressure class
Flue resistance
<200Pa
Flue resistan-
ce >200Pa
<5000Pa
The used material must compliant with the following standards:
EN1856 for metal materials (Stainless steel and aluminum)
EN14471 for plastic materials.
The maximum horizontal flue gas way is 20m. With horizontal ways longer than 20m, a faultless burner start in cold condi-
tion can not be guaranteed.
The maximum negative flue pressure, which does not affect the burner modulation ratio, is 30Pa. Higher negative pressure
will lead to limitation of the burner modulation ratio.
All manuals and user guides at all-guides.com
Calculation base:
Total connection length in boiler room ≤ 1.5 m; 1x
87°-bend
Maximum permissible lenght (m) of flue gas system
Boiler Type
Ø130
Ø150
115-150
50
50
200
42
50
250
48
300
25
350-400
500
570
90°/87° bend: -2,5 meters
45°/43° bend: -1,5 meters
Temperature
class
P1
Min: T120
H1
Min: T120
Dimensioning
Ø200
Ø250
Ø300
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
Condensate
Corrosion class
resistant
W
W
The flue gas system has to be desi-
gned and calculated to guarantee
that the correct materials are used
and that the boiler can work cor-
rectly.
The following table shows the maxi-
mum vertical flue length in combi-
nation with 1 bend, maintaining the
flue resistance below 200Pa.
The table is only an indication of the
possible length. Calculation done
with rigid tube and exit without cap
("free" opening).
In order to choose the correct flue
material, the maximum flue pres-
sure has to be calculated. Below
table shows the different pressure
classes and their limits.
Fire resistant
V1, V2 or
E or
Vm
higher
V1, V2 or
E or
Vm
higher
23
EN