Télécharger Imprimer la page

Electrical Connection; Start-Up; General Information; Preparation - Dimplex SI 5MS Instructions D'installation Et D'utilisation

Publicité

Les langues disponibles

Les langues disponibles

The heat source system must be de-aerated and checked for
leaks.
ATTENTION!
The brine solution must contain at least a 25 % concentration of a
monoethylene glycol or propylene glycol-based antifreeze, which must
be mixed before filling.

7.4 Electrical Connection

The following electrical connections must be established on the
heat pump:
Connection of the control line to the control panel of the heat
pump via terminal X1: L/N/PE.
Connection of the mains cable to the control panel of the
heat pump via terminal X6: L/N/PE.
Connection of the brine circulating pump (to be provided by
the customer) to the control panel of the heat pump via ter-
minal X1: PE and pump contactor K5: 2/4.
All electrical components required for the operation of the heat
pump are located on the control panel.
For detailed instructions on how to connect the heat pump con-
troller and how it functions (e.g. external wall sensor included in
the scope of supply), please refer to the operating manual sup-
plied with the controller.
A disconnecting device with a contact gap of at least 3 mm (e.g.
utility blocking contactor or power contactor) as well as a 1-pole
circuit breaker have to be provided by the customer. The re-
quired conductor cross-section is to be selected according to the
power consumption of the heat pump, the technical connection
requirements of the respective utility company as well as all ap-
plicable regulations. Details on the power consumption of the
heat pump are listed on both the product information sheet and
the type plate. The connection terminals are designed for a max.
conductor cross-section of 10 mm
8

Start-up

8.1 General Information

To ensure that start-up is performed correctly, it should only be
carried out by an after-sales service technician authorized by the
manufacturer. This may be a condition for extending the guaran-
tee (see Warranty Service).

8.2 Preparation

The following items need to be checked prior to start-up:
All of the heat pump connections must be established as de-
scribed in Chapter 7.
The heat source system and the heating circuit must have
been filled and checked.
The dirt trap must have been inserted in the brine inlet of the
heat pump.
All valves that could impair proper flow in the brine and heat-
ing circuits must be open.
The heat pump controller must be adapted to the heating
system in accordance with the controller's operating instruc-
tions.
www.dimplex.de
All manuals and user guides at all-guides.com
2
.

8.3 Start-Up Procedure

The heat pump is started up via the heat pump controller.
ATTENTION!
The heat pump must be started up in accordance with the installation and
operating instructions of the heat pump controller.
If an overflow valve is fitted to maintain the minimum heating
water flow rate, the valve must be adapted to the requirements of
the heating system. Incorrect adjustment can lead to faulty oper-
ation and increased energy consumption. We recommend carry-
ing out the following procedure to correctly adjust the overflow
valve:
Close all of the heating circuits that may also be closed during
operation (depending on the type of heat pump usage) so that
the most unfavourable operating state - with respect to the water
flow rate - is achieved. This normally means the heating circuits
of the rooms on the south and west sides of the building. At least
one heating circuit must remain open (e.g. bathroom).
The overflow valve should be opened far enough to produce the
maximum temperature spread between the heating flow and re-
turn flow listed in the table below for the current heat source tem-
perature. The temperature spread should be measured as close
as possible to the heat pump. The heating element of mono en-
ergy systems should be disconnected.
Heat source
Max. temperature spread
temperature
between heating flow and return
From
To
-5 °C
0 °C
1° C
5° C
6° C
9° C
10° C
14° C
15° C
20° C
21° C
25° C
Any faults occurring during operation are displayed on the heat
pump controller and can be corrected as described in the operat-
ing manual of the heat pump controller.
8.3
flow
10 K
11 K
12 K
13 K
14 K
15 K
E-5

Publicité

loading

Ce manuel est également adapté pour:

Si 7msSi 9msSi 11msSi 14ms