Electrical Connection - Dimplex SI 35TUR Instructions D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

English
7.4.4 Hydraulic distribution system
The compact manifold and the dual differential pressureless
manifold function as an interface between the heat pump, the
heating distribution system, the buffer tank and, in some cases,
even the domestic hot water cylinder. A compact system is
used to simplify the installation process, so that a lot of different
components do not have to be installed individually. Further in-
formation can be found in the relevant installation instructions.
Compact manifold
The return sensor can remain in the heat pump, or should be in-
stalled in the immersion sleeve. The remaining empty space be-
tween the sensor and the immersion sleeve must be filled com-
pletely with heat transfer compound.
Dual differential pressureless manifold
In order for the heating circuit pumps of the generator and con-
sumer circuits to supply the flow to the return sensor, this must
be installed in the immersion sleeve of the dual differential
pressureless manifold.

7.5 Electrical connection

7.5.1 General
All electrical installation work must be carried out by a trained
electrician or a specialist for the specified tasks in accordance
with the
installation and operating instructions,
country-specific installation regulations (e.g. VDE 0100),
technical connection conditions of the energy suppliers
and supply grid operators (e.g. TAB) and
local conditions.
To ensure that the frost protection function of the heat pump
works properly, the heat pump manager must remain con-
nected to the power supply and the flow must be maintained
through the heat pump at all times.
The switching contacts of the output relay are interference-
suppressed. Therefore, depending on the internal resistance of
the measuring instrument, a voltage can also be measured
when the contacts are open. However, this will be much lower
than the line voltage.
Extra-low voltage is applied to controller terminals N1-J1 to N1-
J11; N1-J19; N1-J20; N1-J23 to N1-J26; N17-J1 to N17-J4;
N17-J9; N17-J10; N0-J2 to N0-J14 and the terminal strips X3
and X5.1. If, due to a wiring error, the line voltage is mistakenly
connected to these terminals, the heat pump manager will be
destroyed.
EN-8
7.5.2 Electrical installation work
1)
The 4-core electrical supply cable for the output section of
the heat pump is fed from the heat pump meter via the util-
ity company blocking contactor (if required) into the heat
pump.
Connection of the mains cable to the contact plate of the
heat pump via terminals X1: L1/L2/L3/PE.
An all-pole disconnecting device with a contact gap of at
least 3 mm (e.g. utility blocking contactor or power contac-
tor) and an all-pole circuit breaker with common tripping
for all external conductors must be installed in the power
supply for the heat pump (tripping current and characteris-
tic in compliance with the device information).
ATTENTION!
Ensure the rotary field is clockwise when connecting the
mains cables (if the rotary field is not clockwise, the heat
pump will not work properly, is very loud and may cause
damage to the compressor).
2)
The three-core supply cable for the heat pump manager
(heating controller N1) is fed into the heat pump.
Connection of the control cable to the contact plate of the
heat pump via terminal X2: L/N/PE.
Details on the power consumption of the heat pump are
listed on both the product information sheet and the type
plate.
The supply cable (L/N/PE~230 V, 50 Hz) for the heat pump
manager must have a continuous voltage. For this reason,
it should be tapped upstream from the utility blocking con-
tactor or be connected to the household current, because
otherwise important protection functions could be lost
during a utility block.
3)
The utility blocking contactor (K22) with 3 main contacts
(1/3/5 // 2/4/6) and an auxiliary contact (NO contact 13/
14) should be dimensioned according to the heat pump
output and must be supplied on-site.
The NO contact of the utility blocking contactor (13/14) is
looped from terminal strip X3/G to controller N1/J5-ID3.
CAUTION! Extra-low voltage!
4)
The contactor (K20) for the immersion heater (E10) of
mono energy systems (HG 2) should be dimensioned ac-
cording to the radiator output and must be provided on-
site. It is controlled (230 V AC) from the heat pump man-
ager via terminals X2/N and contact N1/J13-NO4 on the
heat pump manager.
5)
The contactor (K21) for the flange heater (E9) in the do-
mestic hot water cylinder should be dimensioned accord-
ing to the radiator output and must be provided on-site. It
is controlled (230 V AC) from the heat pump manager via
terminals X2/N and contact N1/J16-NO10.
6)
The contactors mentioned above in points 3, 4 and 5 are
installed in the electrical distribution system. Mains cables
for installed heating systems must be designed and pro-
tected in accordance with the valid standards and regula-
tions.
7)
All installed electric cables must have permanent wiring.
8)
The heat circulating pump (M13) is activated via the con-
tact N1-J13/NO5. Connection points for the pump are
coupling relays KM13/14 and X2/N.
9)
The auxiliary circulating pump (M16) is activated via the
contact N1-J16/NO9. Connection points for the pump are
coupling relays KM16/14 and X2/N.
452237.66.54 · FD 9912
SI 35TUR
www.gdts.one

Publicité

Table des Matières
loading

Table des Matières