Please read immediately

1.1 Important information

ATTENTION!
Work on the heat pump must only be performed by
authorised and qualified after-sales service technicians.
ATTENTION!
When operating or maintaining a heat pump, the legal
requirements of the country where the heat pump is operated
apply. Depending on the refrigerant fill quantity, the heat
pump must be inspected for leaks at regular intervals by a
certified technician, and these inspections must be recorded.
ATTENTION!
If the heat pump or circulating pumps are controlled
externally, a flow rate switch is required to prevent the
compressor from being switched on when there is no volume
flow.
ATTENTION!
The heat pump must not be tilted more than 45° (in any
direction).
ATTENTION!
Before commissioning, the transport fastening must be
removed.
ATTENTION!
Flush the heating system prior to connecting the heat pump.
ATTENTION!
The maximum test pressure in the heating circuit and the
brine circuit is 6.0 bar). This value must not be exceeded.
ATTENTION!
With fully demineralised water, it is important to ensure that
the minimum pH value of 7.5 (minimum permissible value for
copper) is complied with. Failure to comply with this value can
result in the heat pump being destroyed.
ATTENTION!
The supplied dirt trap must be inserted in the heat source inlet
of the heat pump to protect the evaporator against the ingress
of impurities.
ATTENTION!
It is recommended that the brine circuit side be equipped with
the flow rate switch available as an option.
ATTENTION!
The brine solution must contain at least a 25 % concentration
of a monoethylene glycol or propylene glycol-based frost
protection, which must be mixed before filling.
ATTENTION!
Ensure the rotary field is clockwise when connecting the
mains cables (if the rotary field is not clockwise, the heat
pump will not work properly, is very loud and may cause
damage to the compressor).
ATTENTION!
It is not permitted to connect more than one electronically
regulated circulating pump via a relay output.
EN-2
ATTENTION!
Commissioning must be performed in accordance with the
installation and operating instructions of the heat pump
manager.
ATTENTION!
Disconnect all electrical circuits from the power source prior
to opening the device.

1.2 Intended use

This device is only intended for use as specified by the manu-
facturer. Any other use beyond that intended by the manufac-
turer is prohibited. This requires the user to abide by the rele-
vant project planning documents. Please refrain from
tampering with or altering the device.