Branch Circuit Protection
Motor Overload Protection
Surrounding Air Temperature Rating
Wiring Diagrams
Micro-environmental pollution conditions
66
Notice d'exploitation – MOVIMOT
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
For maximum branch circuit protection see table below.
SCCR: 65 kA /500 V when protected by
Non-semiconductor fuses
(currents are maximum values)
40 A max./600 V
The devices are provided with load and speed-sensitive overload protection and ther-
mal memory retention upon shutdown or power loss.
The trip current is adjusted to 150% of the rated motor current.
The devices are suitable for an ambient temperature of 40 °C, max. 60 °C with de-ra-
ted output current. To determine the output current rating at temperatures above
40 °C, the output current should be de-rated by 3 % per K between 40 °C and 60 °C.
For wiring diagrams, refer to chapter "Electrical Installation".
For use in pollution degree 1 or 2 micro-environmental conditions only.
®
advanced
Inverse time circuit breakers
(currents are maximum values)
40 A max./500 V min.