Commissioning

Possible settings by INTERBUS master

Possible settings by INTERBUS master
)
Note!
If switches (S1 ... S8) remain in the Lenze setting OFF, the configurations set
under the codes C1910, C1911 and C1912 will become active when the device
is switched on.
Switch off the voltage supply of the communication module and afterwards on again to
activate changed settings.
Please note:
ƒ Impermissible settings are indicated by the yellow LED (communication) (^ 69).
ƒ As a maximum, the data word sum (PCD + PCP) is to amount to 10 words.
ƒ Index determination: 24575 − Lenze code number (Cxxxx)
Codes for configuration
Code
Values
C1910
2 ... 20 (1 ... 10 words)
C1911
0: AIF−CTRL device control
1: DRIVECOM control
C1912
Number of
parameter data
words (PCP)
0
1
2
4
66
ID code
0x03
0xE3
0xE0
0xE1
l
Explanation
Number of process data bytes
(2 process data bytes = 1 process data
word)
Operation with AIF−CTRL device control
or
operation with DRIVECOM profile 21
Number of parameter data words (PCP)
EDKMF2113 DE/EN/FR 5.1