the gate closing.
PEDESTRIAN command (PED BUTT - COM)
This command is useful to open the gate partially, just enough, for
example, to permit a pedestrian crossing. In fact, the Pedestrian
command (see Point E) is carried out only by opening the gate just
enough for a pedestrian to pass, as described into the Point E
procedure.
From the Pedestrian opening position the Automatic Closing can be
enabled or disabled with DIP3.
From the Pedestrian opening position, the gate can be completely
opened by the OPEN or by the K BUTT button or by the RADIO
button.
AUTOMATIC CLOSING (from the COMPLETE open position)
The Automatic Closing from the complete open position can be
enabled turning ON the DIP3.
The maximum gap of time that can be programmed is 5 minutes
(see Point D).
AUTOMATIC CLOSING (from the PEDESTRIAN open position)
The Automatic Closing from the pedestrian open position can be
enabled turning ON the DIP3. The maximum gap of time that can
be programmed is 5 minutes (see Point E).
F
UNCTIONING OF SAFETY ACCESSORIES
PHOTOCELL (PHOT - COM)
In case the switch DIP4 is in the OFF position, the photocells are active
both in gate opening and in gate closing. In this configuration, if an
obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will stop and will restart opening
when the obstacle is removed
- while the gate is still, it will not move neither in opening nor in closing.
In case of the switch DIP4 is in the ON position, the photocells are
active only in gate closing.
In this configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will continue open
- while the gate is still, it will open if a open command is request, it will
remain still if a close command is request.
The photocell input (PHOT - COM) is a NORMALLY CLOSED contact.
In case there are more couple of photocells, the contacts from all the
photocell receivers must be connected in series.
In case the photocells are not installed, this contact must be short circuited
with a wire jump (from PHOT to COM) to permit the gate to operate.
SAFETY STRIP (EDGE - COM)
If an obstacle presses the safety strip:
- while the gate is still, it will not move neither in opening nor in closing
- while the gate is closing, the gate will open
- while the gate is opening, the gate will close.
In case the safety strip is held pressed a further quick reversion, after 2
seconds, is performed. The gate interrupts any movement and this
alarm state will be signalled by both the Blinker and the Buzzer, if
installed, which will remain on for 1 minute. The normal gate operations
can be restored by pressing any push button or radio commands.
The safety strip input (EDGE - COM) is a NORMALLY CLOSED
contact. In case there are more than one safety strip, all their contacts
must be connected in series.
In case the safety strip is not installed, this contact must be short
circuited with a wire jump (from EDGE to COM) to permit the gate
to operate.
TESTING THE SAFETY STRIP equipment
The DIP10 ON enables to test the safety strip equipment. The test is
performed every time the gate completes a full opening. The test is
available only if the safety strip device is equipped with a dedicated
power supply input.
In fact, the safety strip equipment power supply input can be connected
to the D+TEST and D- outputs (DIP10 ON). Automatically, every time
the gate completes a full opening, just before closing, the control board
switches OFF the D+TEST and D- power supply output for a very short
time. While the safety strip power supply is switched OFF, if everything
is working fine the safety strip contact (EDGE - COM) must open. In
case the test fails, no other gate manoeuvre will be allowed and the
alarm state will be signalled by both the Blinker and the Buzzer, if
installed, which will remain on for 5 minutes
NOT ALL THE
SAFETY STRIPS CAN
SWITCH DIP10 MUST BE LEFT OFF.
STOP BUTTON
If the Automatic command is enabled (DIP 6 OFF), a Normally Closed
contact could be connected in series to the COM wire of the opened
and the closed limit switches.
This contact works like a STOP button to interrupt any gate manouver.
FLASHING LIGHT
Connect the flashing light to J7 flashing light outputs, use flashing lights
ACG7059 and bulbs of 40W maximum.
NB: This electronic K board can only supply power to FLASHING
LIGHTS with inbuilt flashing circuit.
PRE-FLASHING function
The DIP 5 in the ON position enables the pre-flashing, the FLASHING
LIGHT and BUZZER starts working 3 seconds before every movement
of the gate.
The DIP 5 in the OFF position disables any pre-flashing, the FLASHING
LIGHT, the BUZZER and the motor will start at the same time.
BUZZER
The current supplied to the Buzzer will be 200 mA at 12Vdc.
During the normal operation of the gate, opening and closing, the
buzzer will buzz intermittently. Only during the alarm situations (safety
strip) the buzzing will almost be constant.
GATE OPEN INDICATOR (D negativo - LSC)
It is turned ON when the gate is open or partially open, it is turned OFF only
when the gate is completely closed.
N.B.: connect in series to the indicator a resistance of 2K2. WE
RECOMMEND NOT TO OVERLOAD THE INDICATORS OUTPUT
OTHERWISE THE GATE FUNCTIONING COULD BE COMPROMISED
OR THE CONTROL BOARD COULD BE DAMAGED.
T
ECHNICAL SPECIFICATIONS
Temperature range
Humidity
Power supply voltage
upon request)
Frequency
Interruptions in electricity supply
Maximum load of motor outputs
Maximum load of blinker output with resistive load
Maximum control board absorption (without accessories)
Current available for photocells and accessories
IP protection grade
Control board weight
Dimensions
TECHNICAL RADIO SPECIFICATIONS (model CRX)
Reception frequency
Impedance
Sensitivity
Time of excitation
Time of discharge
Memory available
Maximum load of radio receiver output
- All inputs shall be used as clean contacts without earthing, because
the power supply is generated in the card and is structured in such a
way to guarantee the respect of double and reinforced insulation to the
elements under voltage
- All inputs are managed by a programmed circuit that carries out a
self-control every time the gate is operated.
G G
B B
BE TESTED, THUS THE
-10 ÷ +55°C
< 95% without condensation
230V~ ±10% (120V/60Hz
50/60 Hz
20ms
1CV
40W
33 mA
0,4A±15% 12Vdc
IP54
0,55 kg
130 x 50 x 115 mm
433,92MHz
52 OHM
>2,24 V
300ms
300ms
60codes
200mA 12Vdc