Warning messages after parameter identification
Code
SA011 Current control setting, no typical value; see Operating Instructions
SA012 Current control setting, no typical value at 2 kHz; see Operating Instructions
SA014 Current control setting, no typical value at 4 kHz; see Operating Instructions
SA018 Current control setting, no typical value at 8 kHz; see Operating Instructions
SA021
Stator resistance (SA021) or rotor resistance (SA022) is very high. The follow-
SA022
ing causes are possible:
The motor cable cross-section is not sufficient.
The motor cables are too long.
The motor cables are not connected correctly.
The contacts are not in a proper condition (corrosion).
SA031 Shorten Motor Line using Switch freq. 16 kHz.
GB
SA033 Shorten Motor Line using Switch freq. 8 kHz and higher.
SA041 The slip speed was not determined correctly. Check the values for parameters
Rated Speed
SA042 The slip speed was not determined correctly. Check the values for parameters
Rated Speed
Warning messages after parameter identification
Code
SA051 The machine data for star connection were entered, the motor, however, is
connected in delta. For star operation, change the motor cable connection. For
delta operation, check the entered rated motor values.
Repeat the parameter identification
SA052 The machine data for delta connection were entered, the motor, however, is
connected in star. For delta operation, change the motor cable connection. For
star operation, check the entered rated motor values.
Repeat the parameter identification
SA053 A phase asymmetry was measured. Check the cables at the terminals of the
motor and the frequency inverter for proper connection and check the con-
tacts for corrosion.
SA054 Resolver offset not adjusted.
Code
SF000 No Error
SF001 The value entered for parameter
value.
SF002 The value for parameter
ters
Rated Mech. Power
128
372 and
Rated Frequency
372 and
Rated Frequency
Error messages during guided commissioning
Rated Current
Quick Start Guide ANG
Meaning / Measure
375.
375.
Meaning / Measure
Meaning / Measure
Rated Current
371 is too high, referred to parame-
376 and
Rated Voltage
371 is too low. Correct the
370. Correct the values.