4.4
X13 connection in ANG510 and ANG610
When an ANG510
is required.
GB
4.5 Installation notes acc. to UL508c/UL 61800-5-1
NOTICE
No branch circuit protection
Integral solid-state short circuit protection does not provide branch
circuit protection.
For an installation according to UL508c / UL 61800-5-1 the motor must be
supervised regarding the thermal behavior. The connection and the parameter
settings for the temperature motor supervision is described in chapter "Ther-
mocontact" in the Operating instructions document.
Thermal motor protection as per UL508c / UL 61800-5-1 can be realized in
devices marked with "TM included" under the rating plate.
Overload protection operates over 100% of the full load current rating of the
motor. The drive parameter shall be set at no more than the full load current
rating of the motor. Motor overtemperature protection is provided.
Drives without inscription "TM included" on name plate only: "Motor over-
temperature sensing is not provided by the drive". For installation as per
UL508c / UL 61800-5-1,
112
or
ANG610
device is used, connection of AC 3x400 V at X13
X13
Branch circuit protection must be provided in accordance with
the Manufacturer Instructions, National Electrical Code and any
additional local codes.
Quick Start Guide ANG
Auxiliary voltage terminal
X13
1 ... 6
7
8
9
10
Connection
Connected load
Supply voltage
Supply frequen-
cy
Not used
PE
L1
L2
L3
≥ 1.2 kW
400 V +- 10
%
50 / 60 Hz
07/20