Télécharger Imprimer la page

BONFIGLIOLI Vectron ACTIVE ANG 410-05 1 FA Guide Rapide page 125

Publicité

Les langues disponibles
  • FR

Les langues disponibles

7.1
Warning and error messages during operation
The code displayed via parameter
composed of several messages. Key A0088 signals warnings
A0008 + A0080, for example.
Key
Meaning
A0000 No warning present.
A0001 Frequency inverter overloaded, warning code (A0002 or A0004)
A0002 Frequency inverter overload (60 s). Check load behavior.
A0004 Short-term overload (1 s). Check motor and application parameters.
A0008 Max. heat sink temperature reached, check cooling system and fan.
A0010 Max. interior temperature reached, check cooling system and fan.
A0020 Speed set point is limited by a controller.
A0080 Max. motor temperature reached, check motor and sensor.
A0100 Mains phase failure, check mains fuses and supply cable.
A0400 Limit frequency reached; output frequency is limited.
A4000 DC link voltage has reached the type-specific minimum.
A8000 Application-specific warning: For detailed functions, refer to Operating Instruc-
tions.
259 and
Current Error
easier, an error code is displayed.
The error message can be acknowledged via the control unit
buttons and STO input.
Key
Meaning
F00 00 No fault has occurred.
F01 02 Frequency inverter overloaded (60 s), check load behavior
03 Short-term overload (1 s), check motor and application parameters
F02 00 Heat sink temperature too high, check cooling system and fan.
01 Temperature sensor defective or ambient temperature too low.
F03 00 Interior temperature too high, check cooling system and fan.
01 Interior temperature too low, check control cabinet heating.
F04 00 Motor temperature too high or sensor defective, check connection
S6IND.
07/20
Warnings
Warning messages
310 make troubleshooting
Last Error
Error messages
Overload
Heat sink
Interior
Motor connection
Quick Start Guide ANG
269 can be
GB
125

Publicité

loading