the mains feeder may be protected using approved fuses only. For
approved fuses, refer to Chapter "Technical data".
the maximum temperatures specified in Chapter "Technical data"
must not be exceeded.
only copper cables with a rated current of 60/75°C may be used.
the devices may only be used in "Pollution Degree 2" environments.
According to UL508c / UL 61800-5-1, warnings and markings/labels must not
be removed.
Short-circuit current rating (SCCR)
For Size 1 to 6
Suitable for use on a circuit capable of delivering not more than 5,000 rms
symmetrical amperes, 480 V AC maximum when protected by K5 Class Fuses.
For Size 7
Suitable for use on a circuit capable of delivering not more than 10,000 rms
symmetrical amperes, 480 V AC maximum when protected by RK5 Class Fuses
or R/C (JFHR2) Semiconductor Fuse, Type FWH-xxxA, manufactured by
Cooper Bussmann LLC.
For Size 8 -51, -53, -55
Suitable For Use On A Circuit Capable Of Delivering Not More Than 18 kA rms
Symmetrical Amperes, 480 V AC Maximum when protected by Semiconductor
fuses Types 170M5* made by Cooper Bussmann LLC.
For Size 8 -57, -59, -61
Suitable For Use On A Circuit Capable Of Delivering Not More Than 30 kA rms
Symmetrical Amperes, 480 V AC Maximum when protected by Semiconductor
fuses Types 170M5* made by Cooper Bussmann LLC.