Parameter
6.1
Description of parameters relevant to ANG
The parameters are partly set via the guided commissioning. The fol-
lowing overviews refer to configurations 110 and 410. For additional
configurations enabling setting of other parameters, refer to the Op-
erating Instructions.
6.1.1
No.
Description
GB
28
Control Level
30
Configuration
34
Program(ming)
369 Motor Type
370 Rated Voltage
371 Rated Current
372 Rated Speed
374 Rated Cosinus Phi -
375 Rated Frequency
Rated mech. Rated
376
power
Switching frequen-
400
cy
118
Adjustable parameters
Parameters relevant to ANG
Unit
These instructions describe the parameters on Control
Level 1. Higher control level parameters are described
-
in the Operating Instructions and should only be set by
expert users.
The basic function of the control inputs and outputs as
well as the assignment of the software modules is
-
selected by the configuration. The selection is made
during the guided commissioning.
The factory settings of all parameters is restored or a
-
fault message is acknowledged (alternative to signal at
digital input STO).
Selection of connected motor or transformer. The
-
selection is considered in the test of the entered rated
values and the guided commissioning.
Enter the voltage indicated on the type plate of the
V
asynchronous motor.
Enter the rated current indicated on the type plate of
A
the asynchronous motor for the selected circuit.
Enter the motor speed indicated on the type plate of
RPM
the asynchronous motor at rated frequency.
Enter the cos(ϕ) value indicated on the type plate of
the asynchronous motor.
Enter the rated frequency (at parameterized rated
Hz
speed) indicated on the type plate of the asynchronous
motor.
Enter the power (in KW) indicated on the type plate of
kW
the asynchronous motor.
The default switching frequency settings depend on
configuration (Config.
Hz
4 kHz). Higher switching frequencies reduce the motor
noise, but reduce the output current (refer to technical
data in Operating Instructions)
Quick Start Guide ANG
Explanation
: 2 kHz, Config.
110
:
410
07/20