Connecting The Device To The Power Grid - Kaco blueplanet 15.0 TL3 Mode D'emploi

Masquer les pouces Voir aussi pour blueplanet 15.0 TL3:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 58
AC-side
Max. conductor cross-section
Max. cable cross-section (without wire sleeves)
Length of insulation to be stripped off
Connection type
Fuse protection for installation provided by customer
Fitting for AC connection
Cable diameter for cable fitting
Torque for cable fitting
Interfaces
Interface screw connections
Cable diameter for cable fitting
RS485 connection type
RS485 terminal cable cross-section
Ethernet connection type
Torque for cable fitting
Overvoltage protection
Overvoltage protection for DC plug (integrated)
Base integrated
7.5

Connecting the device to the power grid

7.5.1 Make the grid connection
TN-S-System, TN-C-S-System, TT-System
↻ Connection cable with 5 strands is provided on the device.
↻ Nominal grid voltage matches the VAC nom name plate details.
1 Loosen cable fitting for AC connection. [ W_46]
2 Remove the outer cladding of the AC cables.
3 Insert the AC cables through the cable fitting into the connection area.
4 Strip the insulation from the AC cables.[sl 18 mm]
5 Open the lock on the printed circuit board connection terminal.
6 Connect cables in accordance with the labels beneath the connection terminal.
7 Close the lock on the printed circuit board connection terminal.
8 Check that all connected cables are fitted securely.
9 Tighten the cable fitting. [ W_46 /
» Make the grid connection.
NOTE
An AC-side disconnection unit must be provided during the final installation stage. This disconnecter mech-
anism must be installed so that it can be accessed at any time without obstruction.
Page 18
10 mm²
16 mm²
18 mm
Spring-type terminals
at least 32 A at 6.0 mm²
M40
16 - 28 mm
7.5 Nm
Ethernet: M25, default RS485: M16, max. 1.5 mm
(2x) 8 - 17 mm
Spring-type terminal
0.25 - 1.5 mm²
RJ45
5 (M25) 2.5 (M16) Nm
Type [KACO article no.]
VAL-MS-T1/T2 1000DC-PV-ST - 2801162 [3010608] – SPD I +
II
VAL-MS 1000DC-PV-ST – 2800624 [23700379] – SPD II
VAL-MS/2+V-BE FM-PU40 – [2908425] – Phoenix Contact
7.5 Nm]
1
2
PE
N
L1
L2
L3
GNYE
BU
BN
BK
GY
Fig. 10: AC connection terminal, 5-
pin
1
Connection terminal
2
Labelling
3
Colour code
KACO blueplanet 15.0 TL3 KACO blueplanet 20.0 TL3