CAUTION
Damage to the PV generator in case of faulty configuration of the DC connector.
A faulty configuration of the DC connector (polarity +/-) causes equipment damage in the DC connection if
it is connected permanently.
›
Please check polarity (+/-) of the DC connector before connecting the DC generator.
›
Before using the solar modules, check the vendor's calculated voltage values against those actually
measured. The DC voltage of the PV system must not exceed the maximum no-load voltage at any
time.
Connecting the PV generator
↻ DC plug connector configured and PV generator checked to ensure there is no
ground fault.
1 Remove protective caps from the required DC connection plugs on the under-
side of the device.
2 Connect the the DC plug connectors to the DC positive and DC negative connect-
ors in pairs.
» The device is connected to the PV generator.
7.7
Creating equipotential bonding
↻ The device has been installed on the mount.
1 Undo the cable fitting for housing ground connection [ W_19]
2 Strip the insulation from the equipotential bonding cable.
3 Furnish the stripped cable with an M4 ring cable lug.
4 Lay the equipotential bonding cable onto the grounding point and attach with
the M4 x 10 bolt and lock washer provided [ W_T30/
5 Check that the connected cable is fitted securely.
6 Tighten the cable fitting for the housing ground connection [ W_19 /
Nm].
» The housing is included in the equipotential bonding.
7.8
Sealing the connection area
↻ Grid connection is prepared.
1 Lift the housing cover onto the housing and loosely tighten the fastening screws.
2 Secure the housing cover by tightening the 4 screws in a diagonally opposite se-
quence [ T_30/
10 Nm].
» The device has been mounted and installed.
» Put the device into operation.
Page 22
1
Fig. 17: Connection for DC positive
and DC negative
2.2 Nm].
2.5
Fig. 18: Earthing point
1 Earthing bolt
Fig. 19: Closing the housing cover
1
2
KACO blueplanet 15.0 TL3 KACO blueplanet 20.0 TL3
2
A
B
1
2
3
4
1
1
2
Screw [M6x25]
Screw [M6x55]