NOTE
If a residual current circuit breaker is necessary due to the installation specification, a type A residual cur-
rent circuit breaker must be used.
If the type A is used, the insulation threshold must be set to greater than/equal to (≥) 200kOhm in the
"Parameters" menu Menu.
For questions regarding the appropriate type, please contact the installer or our KACO new energy cus-
tomer service.
NOTE
When the line resistance is high, i.e. long cables on the grid side, the voltage at the grid terminals of the
device will increase in feed-in mode. If the voltage exceeds the country-specific grid overvoltage limit
value, the device switches off.
Ensure that the cable cross-sections are sufficiently large or that the cable lengths are sufficiently
short.
7.6

Connect PV generator to device

7.6.1 Configuring the DC plug connector
a
b
d
2
1
c
5
6
Fig. 11: Insert wires
Key
1
Wire for DC connection
2
Spring
3
Insert
4
Sleeve
↻ Connection area opened.
↻ NOTE: Before proceeding with the isolation ensure that you do not cut any individual wires.
1 Insert isolated wires with twisted ends carefully up to the connection.
NOTE: Wire ends must be visible in the spring.
2 Close the spring so that the spring latches.
3 Slide insert into sleeve.
4 Secure and tighten the cover on the cable fitting [ W_15/
5 Join insert with contact plug.
6 Check latch by lightly pulling on the coupling.
» Make the electrical connections.
NOTE
The permissible bending radius of at least 4x the cable diameter should be observed during installation.
Excessive bending force may negatively impact the protection rating.
All mechanical loads must be absorbed in front of the plug connection.
Rigid adaptations are not permitted on DC plug connectors.
KACO blueplanet 15.0 TL3 KACO blueplanet 20.0 TL3
3
4
Fig. 12: Slide insert into sleeve
5
Cable fitting
6
Contact plug
7
Coupling
1.8 Nm]
7
Fig. 13: Check fastening
Page 19