Connecting The Device To The Power Grid - Kaco Powador 39.0TL3 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 53
AC-side
Length of insulation to be stripped off
Tightening torque
Connection type
Ground conductor connection
Fuse protection for installation provided by customer
Fitting for AC connection
Cable diameter for cable fitting
Torque for cable fitting
Interfaces
Interface screw connections
Cable diameter for cable fitting
RS485 connection type
RS485 terminal cable cross-section
Ethernet connection type
Torque for cable fitting
7.5

Connecting the device to the power grid

7.5.1 Prepare the grid connection
TN-S system
↻ Connection cable with 5 strands is provided on the device.
↻ Nominal grid voltage matches the VAC nom name plate details.
1 Unfasten the cable fitting for the AC connection [ W_46].
2 Remove the outer cladding of the AC cables.
3 Insert the AC cables through the cable fitting into the connection area.
4 Strip the AC lines [approx. 25 mm].
» Make the grid connection.
TN-S system
↻ Connection cable with 5 strands is provided on the device.
↻ Nominal grid voltage matches the VAC nom name plate details.
1 Unfasten the cable fitting for the AC connection [ W_46].
2 Remove the outer cladding of the AC cables.
3 Insert the AC cables through the cable fitting into the connection area.
4 Strip the AC lines [approx. 25 mm].
» Make the grid connection.
Powador 39.0TL3 , Powador 39.0 TL3 M1 , Powador 40.0 TL3 , Powador 48.0 TL3 Park , Powador 60.0 TL3 ,
Powador 72.0 TL3 Park
abhängig von dem eingesetzen Klemmen-Bautyp
2,5 - 4 Nm / 4 - 4,5 Nm (39.0-48.0TL3) Nm
Schraubklemme
M8
100 A bei 35mm² / 63 A bei 16 mm²
M50
11 - 17 (M25) 5 - 9,5 (M16) mm
5 (M25) 2,5 (M16) Nm
Ethernet: M25, Standard RS485: M16, max. 1,5 mm
11 - 17 (M25) 5 - 9,5 (M16) mm
Steckverbinder
0,25 - 1,5 mm²
RJ45
5 (M25) 2,5 (M16) Nm
1
Fig. 21: Terminals
1
AC side
2
DC-side
2
Page 19