Fastening The Mount; Installing And Securing The Device - Kaco Powador 39.0TL3 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 53
2
Protective corners
3
Pallet
6.3

Fastening the mount

CAUTION
Hazard when using unsuitable fixing materials!
If unsuitable fixing materials are used, the device could fall and persons in front of the device may be seri-
ously injured.
Use only fixing materials that are suitable for the mounting base. The fastening materials supplied are
only suitable for masonry and concrete.
Only install the device in an upright position.
C
A
A
B
Fig. 7: Minimum clearances
Key
A
Horizontal distance between two devices: 500 mm
Vertical distance between two devices: 500 mm
B
Distance in front: 1000 mm
6.4

Installing and securing the device

CAUTION
Risk of injury if the device tips over!
Risk of tipping due to high centre of gravity, particularly with the housing doors open.
Anchor the device securely to the ground immediately after positioning it and, if possible, fasten it to
the wall.
Do not open the housing doors until the device has been securely anchored.
NOTE
Power reduction due to heat accumulation!
If the recommended minimum clearances are not observed, the device may go into power regulation
mode due to insufficient ventilation and the resulting heat build-up.
Observe minimum clearances and provide for sufficient heat dissipation.
All objects on the device housing must be removed during operation.
Ensure that no foreign bodies prevent heat dissipation following device installation.
Powador 39.0TL3 , Powador 39.0 TL3 M1 , Powador 40.0 TL3 , Powador 48.0 TL3 Park , Powador 60.0 TL3 ,
Powador 72.0 TL3 Park
5
A
Fig. 8: Installation below PV support system
C
Eyebolts
Vertical distance to an additional device suitable for
wall mounting: 700 mm
Page 15

Publicité

Table des Matières
loading

Table des Matières