Device configuration
56
7.4.3
Alarm limits (NAMUR)
PARAM É NAMUR
The alarm limits are set to NAMUR values at the factory.
These values can
– be used as default values (DEF) or
– be edited freely (EDIT)
The following operating positions can be altered if operating item 'Edit' was selected.
Name
NAMUR 3.6
NAMUR 3.8
NAMUR 20.5
NAMUR 21.0
The Namur limits are indicated in ascending order.
7.4.4
Test (TEST)
PARAM É TEST É Options OFF, OUT, DISP
Certain device functions can be tested automatically.
OFF (default)
Open collector: OUT
Display: DISP
7.5

Service level (SERV)

This level can only be selected after entering the service code.
7.5.1
Resetting the device (reset)
PRSET - perform reset
Service can reset the settings to the default values.
Reset: After selecting YES, the operating parameters are set to the factory default values.
• Options: Yes or No
• Default: No
If the default values are set, the option selected is automatically reset to No.
Description
Value range: 0 to 25.00
Default: 3.60
Value range: 0 to 25.00
Default: 3.80
Value range: 0 to 25
Default: 20.50
Value range: 0 to 25
Default: 21.00