Example: 4 ... 20 mA = 0 ... 60.00
4 mA x( 6000 – 0)
OFSt
=
0
--------------------------------------- -
(20 mA – 4 mA)
Multiplier Calculation (SCAL)
The display range is adapted to the signal range of the input signal with the SCAL multiplier. The
multiplier is calculated with the following equation:
ME – MA
SCAL
=
-------------------
SE – SA
5.3
Linearization of Non-Linear Measurement Values
For measurement of non-linear measurement values, linearization can be set at the instrument with
the help of 10 nodes. The nodes are preset at steps of 10 % each of the measurement value. The
procedure is as follows:
P
Time
Programming instructions for linearization characteristic curve
GOSSEN-METRAWATT
=
– 1500
P
P
P
=
=
P
Normal
Display Mode
Measuring Range
Upper and Lower
Limit Values
calibrate/preset
cod4 to x6x i.e.
linearize curve
st
Enter 1
node value
nd
2
node
th
10
node
cod4 to x5x i.e.
linearization active
17