Camille Bauer Digem f 96x48CK Mode D'emploi page 138

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Message Formats
Message
Meaning
Status Inquiry
10H
Start Byte
Address
DIGEM Address
11H
Status Inquiry Code
Check Sum
Sum of all User Data
16H
Stop Byte
The DIGEM confirms status inquiry with:
E5H
Acknowledgement
Setting Parameters
68H
Start Byte
05H
Message Length
05H
Message Length
68H
Start
Address
DIGEM Address
69H
Inquiry Code
ASCII Code
Parameter Id. Letter
Check Sum
Sum of all User Data
16H
Stop Byte
The DIGEM confirms parameter setting:
E5H
Acknowledgement
Reset
10H
Start Byte
Address
DIGEM Address
01H
Reset Flag
Check Sum
Sum of all User Data
16H
Stop Byte
• Parameter Identification Letters
Parameter
Offset
Scaling Factor
Tare Value
Limit Value LO1
Limit Value HI1
Limit Value LO2
Limit Value HI2
cod1 and cod2
cod3 and cod4
Measurement Value
Display Value
Hysteresis
22
Message
Parameters Inquiry
68H
03H
03H
68H
Address
89H
ASCII Code
Check Sum
16H
The DIGEM confirms parameter inquiry:
68H
05H
05H
68H
Address
80H
ASCII Code
Parameter LO
Parameter HI
Check Sum
16H
Identification Letter
O
S
see note
T
L
H
D
U
A
B
M
see note
E
X
Meaning
Start Byte
Message Length
Message Length
Start
DIGEM Address
Inquiry Flag
Parameter Id. Letter
Sum of all User Data
Stop Byte
Start Byte
Message Length
Message Length
Start
DIGEM Address
Function Code
Parameter Id. Letter
Low-Order Byte
Higher-Order Byte
Sum of all User Data
Stop Byte
GOSSEN-METRAWATT

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Digem f 96x48ek

Table des Matières