Parameter
Delay Time
Minimum Value
Maximum Value
Set Relays
Analog Output
CAL Zero
CAL Full Scale
SCAL Zero
SCAL F.S.
Linearization Nodes:
0 %
10 %
20 %
30 %
40 %
50 %
60 %
70 %
80 %
90 %
100 %
If several parameters are to be transmitted one after the other, a waiting time of at least 200 ms
between messages must be observed.
Notes Concerning Parameters
• Adjustment to Scaling Factor (identification letter S)
The scaling factor which is prescribed by the serial interface is internally divided by 1.6384 (2
the measuring instrument. This must be taken into consideration when setting the scaling factor via
the serial interface.
Example: Scal reference value = 1,000; to be transmitted = 16384
• Scaling factor inquiry (identification letter S)
The measurement instrument transmits the value which has been multiplied by a factor of 1.6384.
Example: transmitted scaling factor = 16384; actual scaling factor = 1.0000
• Measurement value inquiry (identification letter M)
The measuring instrument transmits the measurement values as a16 place binary code. Positive
values are transmitted directly without polarity sign. For negative values the result of 65,536 minus
the measurement value is transmitted. Example: display = –2000, transmitted value: 63,536.
• Operation as remote display (identification letter M)
If identification letter M is used in the protocol for the setting of parameters, the measuring instru-
ment functions as a remote display. The analog-digital converter is deactivated with this command.
If the instrument is to resume its measuring function thereafter, a reset must be carried out via the
serial interface.
GOSSEN-METRAWATT
Identification Letter
Y
I
J
G
K
N
P
Q
a
b
c
d
e
f
g
h
i
j
k
14