For Mode 2.03 : Relay Output For Heating Or Cooling - Helios EUR EC Instructions D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Specification EUR EC
Example for signal out 0 - 10 V (IO Setup: "A2 function" =
Example: Setpoint ventilation 25.0°C, Offset -5.0 K, Pband 10.0 K
S Setpoint Ventilation +/- Offset
R Pband
I Actual value
9.2.5
For mode
2.03
Setting
-1.0 K
OffsetDigitalOut
Setting
1.0 K
Hyst.DigitalOut
Temperature variation with factory setting
If the ambient temperature is lower than the set operating point, the heating remains switched on. If
the ambient temperature exceeds the set operating point of the heating by 2 K (Kelvin), the heating is
switched off. I.e., the release point is situated at the hysteresis value over the operating point.
Example:
Setpoint 15.0 °C, Offset +5.0 K, Hysteresis 2.0 K
ON = 15°C + 5 K = 20 °C
30
28
26
24
22
20
18
16
14
12
10
1
3
5
L-BAL-E274-GB 1914 Index 003
10 V
100 %
Max. Analog Out
50 %
Min. Analog Out
: Relay output for Heating or Cooling
OffsetDigitalOut
Offset Digital Out = Offset for relay output ("K2" is pre-programmed by the factory).
The relay operating point deviates by the adjusted offset of the Setpoint of the ventila-
tion (if relay "K2" not inverted, terminal "21"-"24" bridged).
Setting range: -10.0...+10.0 K
Factory setting: -1.0 K
"0.0 K"
set, i.e. heating
During negative offset value heating
During positive offset value heating
Hyst.DigitalOut
Switching hysteresis of the relay
Setting range: 0...10,0 K, Factory setting: 1.0 K (Kelvin)
OFF = 20°C + 2 K = 22 °C
7
9
11
13
15
17
19
21
23
25
27
[min]
ON
ON
ON
|
6A
20 °C
10 K
30 °C
S
R
"ON"
when: actual value = Setpoint
"ON"
"ON"
|
|
9K
in IO Setup e. g. for controlling a Heating.
Example:
Setpoint 20.0 °C, Offset -5.0 K, Hysteresis 2.0 K
OFF = 15°C + 2 K = 17 °C
30
28
26
24
22
20
18
16
14
12
10
29
1
3
Part.-No.
35/117
|
)
Min. 0 %
Max. = 100 %
Min. 35 %
Max. = 85 %
I
09.05.2007
v_signal_ausgang_0_10_v.vsd
when: actual value = Setpoint - offset
when: actual value = Setpoint + offset
ON = 20°C - 5K = 15 °C