Warm Tech PAP24000 Mode D'emploi page 87

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

(3)Termination must exhaust above the inlet elevation. It is recommended that at least five feet of
vertical pipe be installed outside when the stove is vented directly through a wall. This will create a
natural draft to prevent the possibility of smoke or odor during appliance shut down or power failure
and avoids exposing people or shrubs to high temperatures.
(4)The vent should terminate no less than four feet below, no less than four feet horizontally from, and
no less than one foot above doors and windows, or gravity /ventilation air inlets into the building.
(5)The distance between the bottom of termination and grade should be a minimum of 12".The
distance between the bottom of the terminate and a public walkway should be a minimum of seven
feet.
(6)Locate the vent termination at least two feet away from combustible material such as shrubs,
plants, grass, fences, roof overhangs, and adjacent buildings.
Pellet pipe type PL or L must be used to vent the STOVE. The stove's flue collar is 3"in diameter. An
approved wall thimble or approved ceiling firestop must be used when the pellet pipe passes through
a combustible wall ceiling.
The stove's combustion blower pressurizes and pushes flue gases out the pellet pipe .As a result, all
pipe joints should be locked together or screwed with three screws if the pipe does not have a locking
system and sealed with high temperature silicone.
The pipe should be siliconed and fastened with three screws to the stove's flue collar.
The longer the run of pipe and the more elbows used, the greater the resistance to the flow of flue
gases. Four inch diameter pellet pipe is recommended for pipe runs greater than 15 feet or when a
number of elbows are used.
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYS TEM OF THIS UNIT. DO
NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
Here are some examples of installation in different situation
Horizontal installations that terminate without any vertical sections of pipe are approved;
However, wind may direct flue gases towed the house causing discoloring problems. For this reason,
horizontal and up 5 feet or horizontal and through the eave installations are recommended.

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Pap30000Pap24001

Table des Matières