4.3

Parameter menu

Code
No.
Name
C00
Password entry
C01
Setpoint and control
source
C02
Load Lenze setting
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES
Possible Settings
Lenze Selection
0
0
0
Setpoint source:
0
Analog input (terminal 8; see C34)
1
Code c40 / Code C47
2
Analog input (terminal 8; see C34)
3
Code c40 / Code C47
4
Analog input (terminal 8; see C34)
5
Code c40 / Code C47
6
Analog input (terminal 8; see C34)
7
Code c40 / Code C47
Note
• When C01 = 1, 3, 5, or 7 and C14 = 0...4, 6, 7, use c40 for speed setpoint
• When C01 = 1, 3, 5, or 7 and C14 = 5, use C47 for torque setpoint
• When C01 = 4...7, terminals E2 and E3 must be used for the remote keypad,
selections made for CE2 and CE3 will be ignored.
0
No action/loading complete
1
Load 50 Hz Lenze settings
2
Load 60 Hz Lenze settings
3
Load OEM settings (if present)
WARNING!
C02 = 1...3 overwrites all settings! TRIP circuitry may be disabled! Check codes CE1...
CE3.
Commissioning
999
Visible only when password is active
(see C94)
Control configuration:
Control = terminals
Programming = keypad
Control = terminals
Programming = remote keypad
Monitoring = remote keypad
Control = remote keypad
Programming = remote keypad
Monitoring = remote keypad
• C02 = 1, 2, 3 only possible with
OFF
• C02 = 2 : C11, C15 and C89 = 60
Hz and C87 = 1750RPM
IMPORTANT
1nh
or
13