Troubleshooting and fault elimination
Error
Remote keypad fault
JF
Drive identification fault
n1d
Short-circuit or overload
0C1
Earth fault
0C2
Motor overload (I
0C6
Controller overtemperature
0H
Overvoltage on DC bus
OU
Flying restart fault
rF
Faulty auto-TRIP reset
rSt
Loss of 4-20 mA reference
Sd5
Single phase fault
SF
(1) The drive can only be restarted if the error message has been reset; see c70
NOTE
In the event of an "OC6" (Motor Overload) failure there is a 3-minute delay before resetting is possible.
This is a requirement of UL508C. This delay is intended to allow time for the motor to cool.
If power is removed when the drive is in an "OC6" fault state, when the power is restored the "OC6" fault
will still be present and the delay will still be active even if power was removed for longer than 3 minutes.
22
22
Remote keypad disconnected
Attempt was made to perform motor
calibration before setting C86...C91
Short-circuit
Excessive capacitive charging
current of the motor cable
Acceleration time (C12, c01) too short
Defective motor cable
Internal fault in motor
Frequent and long overload
Grounded motor phase
Excessive capacitive charging
current of the motor cable
2
t overload)
Motor is thermally overloaded, due to:
• impermissable continuous current
• frequent or too long acceleration
processes
Controller too hot inside
Mains voltage too high
Excessively short deceleration time or
motor in generator mode
Earth leakage on the motor side
Controller was unable to synchronize
with motor during restart attempt
More than 8 errors in 10 minutes
4-20 mA signal (terminal 8I) is below 2
mA (C34 = 5)
A mains phase has been lost
Cause
Check remote keypad connections
Must set C86...C91 before performing
motor calibration (see c48)
Find reason for short-circuit; check
motor cable
Use shorter motor cables with lower
charging current
• Increase acceleration time
• Check controller selection
Check wiring
Check motor
Check controller selection
Check motor/motor cable
Use shorter motor cables with lower
charging current
• Check controller selection
• Check setting of c20
• Reduce controller load
• Improve cooling
Check mains voltage
Increase deceleration time or use
dynamic braking option
Check motor/motor cable
(separate motor from controller)
Check motor/load
Depends on the error
Check signal/signal wire
Check mains voltage
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES
Lenze 13466187 EDBTL03 v8 EN, DE, FR, IT, ES
Remedy