Table 5-3 RS485 Data Format
RS485 Data Format
Baud Rate
Data Bit
Stop Bit
Parity
5.5.2 EPO (Emergency Power Off) Connections
The SOLIVIA 15 TL and 20 TL provide 2 sets of emergency power off functions by using an RJ45
connector. When the outer external switch is shorted, the inverter will shut down immediately.
Please see table 5-3 for the pin defi nition.
Table 5-4 EPO pin assignment
PIN
1
2
3
4
5
6
7
8
NOTE: To shutdown the inverter, short pin 1 and 2 or short pin 4 and 5.
Programmable, 2400/4800/9600/19200/38400, default = 19200
8
1
N/A
Defi nition
EPO1
EPO1
N/A
EPO2
EPO2
N/A
N/A
N/A